Component Type (ETIM Class)
Miniature circuit breaker (MCB)
Electrical
Rated current16 A
Number of poles (total)2
Trip curveC
Rated voltage415 V
Frequency50-60 Hz
Voltage typeAC/DC
Service voltage Ub, AC12 V
Rated short-circuit breaking capacity Icn according to AS/NZS 60898 at 400 VAC6 kA
Rated short-circuit breaking capacity Icu according to AS/NZS 60947-2 at 400 VAC10 kA
Max. rated operation voltage Ue440 V
Rated insulation voltage Ui400 V
Rated impulse withstand voltage Uimp6 kV
Concurrently switching neutral conductorYes
Construction
Number of protected poles2
Degree of protection (IP)IP40
Mechanical
Connectable conductor cross section solid-core1-16 mm²
Connectable conductor cross section multi-wired1-10 mm²
Dimensions
Height86 mm
Width18 mm
Width in number of modular spacings1
Depth76 mm
Weight0.16 kg
Environment
Pollution degree3
Rated surrounding temperature without derating30 °C
Ambient temperature during operating-25-55 °C