Acti 9, Arc fault detection RCBO, Acti 9 iDPN H VigiArc, 1P+N, 16 A, 10000 A, 30 mA, type A***EMAIL/TEXT FOR PRICING***

In stock
SKU: A9T27616
Regular price $0.00 inc. GST

View Data Sheet

Specifications

Design

Range

Acti9

Product or component type

arc fault detection RCBO

Sustainable offer status

Green Premium product

Warranty

24 months

Physical

Standards

EN/IEC 62606|AS/NZS 61009.1

[in] rated current

16 A

[ue] rated operational voltage

230/240 V AC 50 Hz conforming to AS/NZS 61009.1|230/240 V AC 50 Hz conforming to IEC 62606

Control type

toggle

Local signalling

ON, OFF, fault trip

Mounting mode

clip-on

Mounting support

DIN rail

Mechanical durability

20000 cycles

Electrical durability

20000 cycles 240 V AC 50 Hz conforming to AS/NZS 61009.1

Cable entry

top and bottom

Connections - terminals

tunnel type terminal for 2 cable(s) 2.5-2.5 mm² rigid|tunnel type terminal for 1 cable(s) 16-16 mm² rigid|tunnel type terminal for 2 cable(s) 2.5-2.5 mm² flexible|tunnel type terminal for 1 cable(s) 10-10 mm² flexible

Wire stripping length

14 mm

Height

91 mm

Width

36 mm

Depth

75 mm

Net weight

205 g

Ip degree of protection

IP20 conforming to IEC 60529

Relative humidity

95 % at 55 °C

Ambient air temperature for operation

-25...60 °C

Ambient air temperature for storage

-40...80 °C

Reach regulation

Reference contains Substances of Very High Concern above the threshold

Eu rohs directive

Compliant with Exemptions

Mercury free

Yes

Rohs exemption information

Yes

China rohs regulation

Product out of China RoHS scope. Substance declaration for your information

Environmental disclosure

ENVPEP2205013EN

Circularity profile

ENVEOLI2205013EN

Others

Package 1 bare product quantity

1

Product name

Acti9 iDPN H VigiARC

Product specific application

arc fault detection

Device short name

iDPN H VigiARC

Poles description

1P + N

Number of protected poles

1

Curve code

C

Breaking capacity

10000 A at 240 V AC 50 Hz conforming to AS/NZS 61009.1

Rated breaking and making capacity

Idm 500 A at 240 V AC 50 Hz conforming to AS/NZS 61009.1

Neutral position

left

Network type

AC

Earth-leakage protection time delay

instantaneous

Earth-leakage protection class

class A

Suitability for isolation

yes

Residual current tripping technology

voltage dependent

Trip unit technology

thermal-magnetic

Earth-leakage protection

integrated

Network frequency

50 Hz

Device location in system

outgoer

Magnetic tripping limit

5...10 x In

Limitation class

3 conforming to AS/NZS 61009.1

[ui] rated insulation voltage

250 V AC 50 Hz between phase and neutral|400 V AC 50 Hz between phases

Threshold tripping voltage

275 V for +/- 5 V

[uimp] rated impulse withstand voltage

4 kV conforming to AS/NZS 61009.1

Contact position indicator

yes

Overvoltage category

III

Locking options description

padlocking device

Tightening torque

2 N.m

Comb busbar and distribution block compatibility

YES

9 mm pitches

4

Heat dissipation

3.40...3.40 W at 240 V - 16 A

Pollution degree

2 conforming to AS/NZS 61009.1|2 conforming to IEC 62606

Tropicalisation

severity B conforming to IEC 60068-2-30 for 28 d

Operating altitude

2000 m

Quality labels

RCM

Unit type of package 1

PCE

Number of units in package 1

1

Package 1 height

7.5 cm

Package 1 width

3.6 cm

Package 1 length

9.1 cm

Package 1 weight

237.0 g

Halogen content performance

Halogen free plastic parts product
Show less

Customer Reviews

Be the first to write a review
0%
(0)
0%
(0)
0%
(0)
0%
(0)
0%
(0)