Specifications

Design

Range

Acti9

Product or component type

residual current breaker with overcurrent protection (RCBO)

Sustainable offer status

Green Premium product

Physical

[in] rated current

20 A at 30 °C

[ue] rated operational voltage

400/415 V

Control type

toggle

Local signalling

ON/OFF indication

Mounting mode

clip-on

Mounting support

DIN rail|chassis

Height

112 mm

Width

54 mm

Depth

77.2 mm

Net weight

462 g

Mechanical durability

20000 cycles

Electrical durability

5000 cycles

Connections - terminals

screw clamp terminal (top) 1-25 mm² rigid without cable end|screw clamp terminal (top) 1-16 mm² flexible

Wire stripping length

power circuit: 11 mm for bottom connection|power circuit: 14 mm for top connection

Standards

AS/NZS 61009.1|IEC 61009-1|IEC 61009-2-2

Ip degree of protection

IP20

Relative humidity

95 % at 55 °C

Ambient air temperature for operation

-5...60 °C

Ambient air temperature for storage

-25...70 °C

Reach regulation

Free of Substances of Very High Concern above the threshold

Reach free of svhc

Yes

Eu rohs directive

Compliant

Rohs exemption information

Yes

China rohs regulation

 Pro-active China RoHS declaration (out of China RoHS legal scope)

Environmental disclosure

ENVPEP2308033EN

Circularity profile

ENVEOLI2308033EN

Others

Commercial status history

SESA602958 | Sun Oct 29 17:35:00 EDT 2023 | From Unitary Local | From 06 to 08

Package 1 bare product quantity

1

Package 2 bare product quantity

16

Circuit breaker application

distribution

Product name

Acti9 iC60 RCBO

Device short name

iC60H3 RCBO

Poles description

3P + Ns

Earthing system

TN

Curve code

C

Earth-leakage sensitivity

100 mA

Breaking capacity

10000 A Icn at 400/415 V

Neutral position

left

Number of protected poles

3

Device location in system

outgoer

Network frequency

50/60 Hz

Network type

AC

Trip unit technology

thermal-magnetic

Residual current tripping technology

voltage dependent

Earth-leakage protection time delay

instantaneous

Earth-leakage protection class

type A

[icw] rated short-time withstand current

Icw: 250 A during 8/20 µs impulse withstand

[ics] rated service breaking capacity

7500 A

Limitation class

3

[ui] rated insulation voltage

500 V

[uimp] rated impulse withstand voltage

4 kV

Surge current

250 A

Suitability for isolation

yes conforming to IEC 61009-1

Comb busbar and distribution block compatibility

YES

9 mm pitches

6

Provision for padlocking

padlockable with padlock Ø 4 mm|lead seal

Locking options description

ON/OFF locking facilities

Tightening torque

power circuit: 2.5...2.5 N.m top|power circuit: 2.5...2.5 N.m bottom

Earth-leakage protection

integrated

Test button operating voltage

260...457 V

Operating voltage earthleakage protection

150...457 V

Grid distance

45 mm

Locking options description

handle sealable with cable diameter 1.4mm in OFF or ON position

Tropicalisation

2

Unit type of package 1

PCE

Number of units in package 1

1

Package 1 height

12.7 cm

Package 1 width

6.6 cm

Package 1 length

9 cm

Package 1 weight

539 g

Unit type of package 2

S02

Number of units in package 2

16

Package 2 height

15 cm

Package 2 width

30 cm

Package 2 length

40 cm

Package 2 weight

9.376 kg