Component Type (ETIM Class)
Power switching circuit breaker
Electrical
Rated current In20 A
Number of poles1
Max. rated operation voltage Ue AC240 V
Rated ultimate short-circuit breaking capacity lcu at 415 V, 50 Hz25 kA
Rated service short-circuit breaking capacity lcs at 415 V, 50 Hz13 kA
Type of protection trip unitThermal/magnetic release
Trip curveFixed thermal, fixed magnetic
Frame size rating160 A
Position of connection for main current circuitFront side
Rated frequency50-60 Hz
Rated insulation voltage Ui690 V
Suitable for isolationYes
Rated impulse withstand voltage Uimp8 kV
Over voltage categoryIV
Reverse connection of supply possibleYes
Electrical life at Un, In (service cycles)10000 cycles
Type of electrical connection of main circuitScrew connection
Power loss3.6 W
Mechanical
Mechanical life (service cycles)20000 cycles
Vibration acceleration (Max)19 m/s²
Vibration frequency, operational (Max)16.7 Hz
Vibration duration (Max)12 min
Dimensions
Cable cross section (range)1.5-35 mm²
Height130 mm
Width25 mm
Pole connection pitch25 mm
Built-in depth68 mm
Depth (toggle included)95 mm
Weight0.3 kg
Environment
Pollution degree3
Rated surrounding temperature without derating50 °C
Rated temperature-5-70 °C
Maximum operating temperature70 °C
Storage temperature-10-70 °C
Allowable relative humidity0-85 %
Altitude before derating (Max)2000 m
Certificates/Approvals
StandardAS/NZS IEC 60947.2