Component Type (ETIM Class)
Power contactor, AC switching
Electrical
Number of normally open contacts as main contact3
Number of normally closed contacts as main contact0
Rated operation current Ie at AC-3, 400 V190 A
Rated operation power at AC-3, 400 V90 kW
Rated operation current Ie at AC-1, 400 V275 A
Max. rated operation voltage Ue AC1000 V
Voltage type for actuatingAC/DC
Rated control supply voltage Us at AC 50HZ24-60 V
Rated control supply voltage Us at DC24-60 V
Number of auxiliary contacts as normally open contact1
Number of auxiliary contacts as normally closed contact1
Rated operation current Ie at AC-3, 690 V135 A
Rated operation power at AC-3, 690 V132 kW
Rated operation current Ie at AC-3, 1000 V85 A
Rated operation power at AC-3, 1000 V110 kW
Rated operation power at AC-4, 400 V63 kW
Rated control supply voltage Us at AC 60HZ24-60 V
Power consumption, AC coil pickup165 VA
Power consumption, AC coil hold-in6 VA
Power consumption, DC coil pickup205 W
Power consumption, DC coil hold-in2.5 W
Type of electrical connection of main circuitBolt connection
Rated operation current Ie at AC-4, 400 V128 A
Construction
Degree of protection (IP)IP00
Mounting methodScrew mounting
Dimensions
Height196 mm
Width105 mm
Depth152 mm
Weight3 kg