Component Type (ETIM Class)
Power contactor, AC switching
Electrical
Number of normally open contacts as main contact3
Number of normally closed contacts as main contact0
Rated operation current Ie at AC-3, 400 V580 A
Rated operation power at AC-3, 400 V355 kW
Rated operation current Ie at AC-1, 400 V800 A
Max. rated operation voltage Ue AC1000 V
Voltage type for actuatingAC/DC
Rated control supply voltage Us at AC 50HZ100-250 V
Rated control supply voltage Us at DC100-250 V
Number of auxiliary contacts as normally open contact1
Number of auxiliary contacts as normally closed contact1
Rated operation current Ie at AC-3, 690 V500 A
Rated operation power at AC-3, 690 V500 kW
Rated operation current Ie at AC-3, 1000 V250 A
Rated operation power at AC-3, 1000 V355 kW
Rated control supply voltage Us at AC 60HZ100-250 V
Power consumption, AC coil pickup880 VA
Power consumption, AC coil hold-in12 VA
Power consumption, DC coil pickup898 W
Power consumption, DC coil hold-in5 W
Type of electrical connection of main circuitBolt connection
Construction
Degree of protection (IP)IP00
Mounting methodScrew mounting
Dimensions
Height273 mm
Width210 mm
Depth242 mm
Weight15 kg