Component Type (ETIM Class)
Power switching circuit breaker
Electrical
Rated current In100 A
Number of poles3
Max. rated operation voltage Ue AC690 V
Rated ultimate short-circuit breaking capacity lcu at 415 V, 50 Hz36 kA
Rated service short-circuit breaking capacity lcs at 415 V, 50 Hz36 kA
Type of protection trip unitElectronic release
Trip curveLSI
Frame size rating160 A
Long time overload protection adjustment range36.8-100 A
Position of connection for main current circuitFront side
Instantaneous protection adjustment range300-1500 A
Rated frequency50-60 Hz
Rated insulation voltage Ui800 V
Suitable for isolationYes
Rated short circuit breaking capacity, Icu 690V AC6 kA
Rated short circuit breaking capacity, Ics 690V AC6 kA
Short time protection adjustment range55.2-1000 A
Rated impulse withstand voltage Uimp8 kV
Over voltage categoryIV
Reverse connection of supply possibleYes
AC power loss per pole at In3.5 W
Electrical life at Un, In (service cycles)30000 cycles
Type of electrical connection of main circuitScrew connection
Power loss10.5 W
Mechanical
DIN rail (top hat rail) mounting optionalYes
Mechanical life (service cycles)50000 cycles
Max. vibration acceleration19 m/s²
Max. vibration frequency, operational16.7 Hz
Max. vibration duration12 min
Dimensions
Cable cross section (range)1.5-70 mm²
Height130 mm
Width90 mm
Pole connection pitch30 mm
Built-in depth68 mm
Depth (toggle included)95.5 mm
Weight1 kg
Environment
Pollution degree3
Rated surrounding temperature without derating50 °C
Rated temperature-5-70 °C
Maximum operating temperature70 °C
Storage temperature-10-70 °C
Allowable relative humidity0-85 %
Max. altitude before derating2000 m
Certificates/Approvals
StandardAS/NZS IEC 60947.2