Overview
1.1 Certificates: CE, KEMA, UkrSEPRO, EAC, RCC, UL;
1.2 Electric ratings: AC 50/60Hz, 690V, 0.1A~630A;
1.3 Tripping class: 10A;
1.4 Mounting version: Plug-in available for NR2-25
1.5 Standard: IEC/EN 60947-4-1
Type designation
Technical data
Catalogue ordering codes | standard | 246919 | |
RoHS | 980019 | ||
Tripping class | 10A | ||
Phase failure protection function | yes | ||
Automatic and manual reset | yes | ||
Temperature compensation | yes | ||
Releasing indicator | yes | ||
Test and stop pushbutton | yes | ||
Mounting mode | plug-in | yes | |
independent | yes | ||
Auxiliary contacts | Number of contacts | 1NO + 1NC | |
Rated current (AC-15 220V) | 2,73А | ||
Rated current (AC-15 380V) | 1,58А | ||
Rated current (DC-13 220V) | 0,2А | ||
Rated operational current | 1~1,6А | ||
Matched fuse | aM | 2A | |
gG | 4A | ||
Cross-section area of conductors | main circuit | single core or stranded wire | 1~4mm2 |
wiring screw | M4 | ||
auxiliary circuit | single core or stranded wire | 0,5~2,5mm2 | |
wiring screw | M3,5 |
Protection properties
Item | Series No. | I/In | Operating time, Tp | Test condition | |
---|---|---|---|---|---|
Overload protection | 1 | 1,05 | > 2h | Start from cold status | |
2 | 1,2 | ≤ 2h | Start from heat status, rigth after item no.1 | ||
3 | 1,5 | ≤ 2min | Start from heat status, rigth after item no.1 | ||
4 | 7,2 | 2s<Tp≤10s | Start from cold status | ||
Phase failure protection | 5 | Any two phases | Another phase | > 2h | Start from cold status |
1,0 | 0,9 | ||||
6 | 1,15 | 0 | ≤ 2h | Start from heat status, right after item no. 5 |